RURALELECTRIFICATIONAIS变电站双母接线电气设备布置方式的优化孙亚辉(国网福建省电力有限公司超高压分公司,福建福州350013)摘要:针对AIS变电站双母接线电气设备布置方式,克服传统设计理念存在的不足,在不增加变电站面积的情况下,提出3种优化设计方案,将电压互感器和避雷器采用共基础结构,改变断路器、电缆沟及端子箱的位置布置,优化隔离开关结构形式,方便大型作业车辆(高空作业、吊车)的使用,可以满足电气设备吊装检修时《国家电网公司电力安全工作规程(变电部分)》规定的安全距离要求,大大降低作业安全风险,提高作业效率。关键词:空气绝缘开关设备;变电站;双母线;电气设备;布置中图分类号:TM645OptimizationofElectricalEquipmentLayoutwithDoubleBusConnectioninAISSubstationSUNYahui(StateGridFujianEHVCompany,FujianFuzhou350013,China)Abstract:AimingatthelayoutofdoublebusconnectionelectricalequipmentinAISsubstation,overcomingtheshortcomingsofthetraditionaldesignconcept,threeoptimizationdesignschemesareproposedwithoutincreasingtheareaofthesubstation.Thevoltagetransformerandlightningarresterareadoptedinthecommonfoundationstructure,thepositionandlayoutofthecircuitbreaker,cabletrenchandterminalboxarechanged,andthestructuralformofthedisconnectorisoptimizedtofacilitatetheuseoflarge-scaleoperationvehicles(aerialoperationandcrane),Itcanmeetthesafetydistancerequirementsspecifiedinthesafetyregulationsduringtheliftingandmaintenanceofelectricalequipment,greatlyreducetheoperationsafetyriskandimprovetheoperationefficiency.Keywords:AIS;substation;doublebus;electricalequipment;layout变电站双母接线[1-4]是一种常见的主接线方式之一,应用非常广泛。空气绝缘的敞开式开关设备(airinsulatedswitchgear,简称AIS)[5-6],仍然大量存在。在变电站面积限定的空间内,AIS电气设备在变电站双母接线方式中的传统布置,虽然满足设计标准[7],但由于没有充分考虑高压电气设备停电检修期间的安全距离问题,给检修人员带来了一定的麻烦和安全隐患,有时需要采取特殊措施或扩大停电范围才能满足检修安全距离要求。针对上述问题,在不增加变电站面积的前提下,提出一些优化设计,既能满足设计标准要求,又能满足检修工作要求。1传统双母接线电气设备布置方式以220kV双母接...