负荷开关—熔断器组合电器转移电流开断试验回路浅析李江,费亚琴,郭强,刘宸(西安高压电器研究院常州有限责任公司,江苏常州213017)摘要:为保证配电系统的安全可靠运行,负荷开关—熔断器组合电器必须进行相应的型式试验。通过对负荷开关—熔断器组合电器转移电流开断试验回路及相关要求的分析,讨论了转移电流(TDItransfer)试验要求以及试验回路的影响因素,并对这些因素的影响程度进行电磁暂态仿真模拟,为今后相关试验应用提供参考。关键词:负荷开关—熔断器组合电器;转移电流(TDItransfer);电源侧阻抗占比;TRVAnalysisofTestCircuitforTransferCurrentBreakingTestsofSwitch⁃fuseCombinationLIJiang,FEIYaqin,GUOQiang,LIUChen(Xi’anHighVoltageApparatusResearchInstituteChangzhouCo.,Ltd.,JiangsuChangzhou213017,China)Abstract:Forensuringsafeandreliableoperationofthedistributionsystem,theswitch⁃fusecombinationsmustun⁃dergocorrespondingtypetest.Throughouttheanalysisofthetestcircuitforbreakingtestsandrelatedrequirementsoftheswitch⁃fusecombination,thetestrequirementsofthetransfercurrent(TDItransfer)andtheinfluencingfactorsofthetestcircuitarediscussed,theelectromagnetictransientsimulationiscarriedouttoevaluatetheeffectsofthesefactors,whichprovidereferenceforfuturerelevanttests.Keywords:switch⁃fusecombination;TDItransfer;supplysideimpedanceratio;TRV0引言高压负荷开关与限流熔断器串联组合成一体的电器称负荷开关—熔断器组合电器(以下称组合电器),该组合电器常用来保护电力变压器[1-2]。高压负荷开关—熔断器组合电器是由熔断器来承担过载电流和短路电流的开断的。组合电器的转移电流取决于熔断器触发高压负荷开关的分闸时间和熔断器的时间—电流特性。当熔断器的过载电流达到转移点区域时,最快熔化的熔体动作形成首相开断,触发撞击器在极短的时间内脱扣器机构联动,同时,其余两相的过载电流将减少至87%,并转移到高压负荷开关来开断,避免了缺相运行[3-5]。目前国网12kV环网柜标准化设计应用量较大的为SF6气体绝缘环网柜,在开断电路时,转移电流往往大于负荷开关的额定电流,且在开断过程中,电源侧与负载侧将同时承受瞬时恢复电压(TRV)的影响,很可能导致电弧无法熄灭,不能起到保护其他电器的作用,组合电器也会因开断失败而损坏甚至危及操作者。...