温馨提示:
1. 部分包含数学公式或PPT动画的文件,查看预览时可能会显示错乱或异常,文件下载后无此问题,请放心下载。
2. 本文档由用户上传,版权归属用户,汇文网负责整理代发布。如果您对本文档版权有争议请及时联系客服。
3. 下载前请仔细阅读文档内容,确认文档内容符合您的需求后进行下载,若出现内容与标题不符可向本站投诉处理。
4. 下载文档时可能由于网络波动等原因无法下载或下载错误,付费完成后未能成功下载的用户请联系客服处理。
网站客服:3074922707
IEC_81_223_CC
81/223/CCCOMPILATION OF COMMENTS ON COMMITTEE DRAFTProject number:IEC 62305-3,Ed.1Reference number of the CD81/214/CDIEC/TC or SCTC 81Date of circulation2003-07-25Title of the TC or SC:Lightning protectionTitle of the committee draft:IEC 62305-3,Ed.1:Protection against lightning-Part 3:Physical damage to structures and life hazardThe above-mentioned document was distributed to National Committees with a request that comments be submittedComments received see annex 1)DECISION OF THE CHAIRMAN(in cooperation with the secretariat)aA revised committee draft will be distributed as a committee draft for vote(CDV)by(date).bA revised committee draft will be distributed for comment by(date).cThe committee draft and comments will be discussed at the next meeting(date)2003-09-29NOTE In the case of a proposal a or b made by the chairman,P-members objecting to such a proposal shall inform the Central Officewith copy to the secretary in writing within 2 months of the circulation of this compilation(see ISO/IEC Directives,Part 1,2.5.3).Name or signature of the SecretaryG.B.Lo PiparoName or signature of the ChairmanC.BouquegneauFORM CC(IEC)2002-08-091)to be collated on Form Comments and annexed.2 81/223/CCAnnexDateDocument2003-07-2581/214/CDNationalCommitteeClause/SubclauseParagraphFigure/TableType ofcomment(General/Technical/Editorial)COMMENTSProposed changeOBSERVATIONS OF THE SECRETARIATon each comment submittedGBEditorialA large amount of editorial work isrequired for this document to beconsistent with the ISO/IEC Directives,Part 2.Particular attention needs to be given toensuring that the language used isconsistent with the status(i.e.normativeor informative)of the text.For example,informative annexes should not useshall.Noted.NLGeneralIn the German standard there is anannex with symbols and drawings ofexamples how to use the symbols.Take the German Annex and make itAnnex G of the document.Not agreed,Cenelec WG2 did a TR withsymbols.We can use that one.We dont place figures in the textbecause it is very difficult to maintain.PLGeneralThe document is well prepared,onlysome small changes are needed.Noted.CNIndtroductionPar2edmost effective,measuremost effective measureAgreed.UnitedStatesIntroduction4th paragraphTechnicalThe United States does not concur withthe addition of“external”before“LPScomponents.”We understand that thechange was made due to a commentforwarded in IEC 81/211/CC,but theaddition of the word adds nothing to therequirement and contradicts statementsin the body of the document.Paragraph5.1.3 allows metal framework of abuilding to be used as a down conductorand most metal framework would not beconsidered“external.”Delete the word“external”from thissentence/paragraph.Not accepted.Separation distance or bonding shall beimplemented toward external LPSaccording to paragraph 6Agreed.UnitedStatesIntroduction5th paragraphEditorialChange“of”to“to”in the introductoryclause in the paragraph.Revise introductory clause as follows:“Main protection measures againstinjuries to living beings”Agreed.3 81/223/CCNationalCommitteeClause/SubclauseParagraphFigure/TableType ofcomment(General/Technical/Editorial)COMMENTSProposed changeOBSERVATIONS OF THE SECRETARIATon each comment submittedUnitedStatesIntroduction5th paragraphpart b)EditorialAdd“s”to“notice”at end of item b).Where notices are used,more than oneis likely to be required.Revise clause as follows:“physical restrictions and/or bywarning notices.”Agreed.UnitedStatesIntroduction7th paragraph,1st sentenceEditorialChange“to form”back to“of forming.”We understand that the change wasmade due to a comment forwarded inIEC 81/211/CC,but the original wordingwas grammatically correct.The noun“purpose”must be modified by anadjective vice an infinitive.“Access to ground and the proper use offoundation steelwork for the purpose offorming an effective earth termination”Agreed.UnitedStatesIntroductionLastparagraphEditorialReplace“for”with“of”in the lastsentence.The sentence is discussingthe design of the LPS not the design forthe LPS.“The design of the type and location ofthe LPS should take into account thefeatures of the existing structure.”Agreed.UnitedStatesScopeFirstparagraphTechnical/EditorialDelete the final clause“outside of thestructure.”Step and touch voltages arerelevant regardless of whether theyoccur inside or outside of a structure.Paragraph 5.1.3 allows metal frameworkof a building to be used as a downconductor.Such lightning currentconductors can lead to step and touchpotentials.It is also recommended that the commaafter“(LPS)”be removed and“the”beadded before“LPS.”“This part of IEC 62305 provides therequirements for protection of a structureagainst physical damages by means of alightning protection system(LPS)and forprotection against injuries to living beingsdue to step and touch voltages in thevicinity of the LPS(see IEC 62305-1).”Agreed.UnitedStatesScopeNote 1Technical/EditorialRevise the second sentence of this noteas proposed.The USNC is not in theposition to co