温馨提示:
1. 部分包含数学公式或PPT动画的文件,查看预览时可能会显示错乱或异常,文件下载后无此问题,请放心下载。
2. 本文档由用户上传,版权归属用户,汇文网负责整理代发布。如果您对本文档版权有争议请及时联系客服。
3. 下载前请仔细阅读文档内容,确认文档内容符合您的需求后进行下载,若出现内容与标题不符可向本站投诉处理。
4. 下载文档时可能由于网络波动等原因无法下载或下载错误,付费完成后未能成功下载的用户请联系客服处理。
网站客服:3074922707
TM_D_3555_
_07_2013
Designation:D355507(Reapproved 2013)Standard Specification forTrack-Resistant Black Crosslinked Polyethylene Insulationfor Wire and Cable,90 C Operation1This standard is issued under the fixed designation D3555;the number immediately following the designation indicates the year oforiginal adoption or,in the case of revision,the year of last revision.A number in parentheses indicates the year of last reapproval.Asuperscript epsilon()indicates an editorial change since the last revision or reapproval.1.Scope1.1 This specification covers a track-resistant black cross-linked polyethylene insulation,the base polymer which con-sists substantially of polyethylene or its copolymers.Thisinsulation shall be carbon black pigmented.1.2 This type of insulation is considered suitable for use onwire or cable that will be used for continuous operation atconductor temperatures up to 90 C.1.3 This insulation is suitable for use on wire or in cableused for power transmission in overhead spaced-line service,installed at temperatures above 25 and exposed to sunlightand other atmospheric environments between 55 and+90 C.1.4 In many instances,the insulation cannot be tested unlessit has been formed around a conductor.Therefore,tests done oninsulated wire in this standard are solely to determine therelevant property of the insulation and not to test the conductoror completed cable.1.5 Whenever two sets of values are presented,in differentunits,the values in the first set are the standard,while those inparentheses are for information only.2.Referenced Documents2.1 ASTM Standards:2D470 Test Methods for Crosslinked Insulations and Jacketsfor Wire and CableD1711 Terminology Relating to Electrical InsulationD2132 Test Method for Dust-and-Fog Tracking and ErosionResistance of Electrical Insulating MaterialsD2765 Test Methods for Determination of Gel Content andSwell Ratio of Crosslinked Ethylene Plastics2.2 ICEA Standard:ICEA T-28-562 Test Method for Measurement of Hot Creepof Polymeric Insulations33.Terminology3.1 Definitions:3.1.1 For definitions of terms used in this specification,referto Terminology D1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging,(act of),nexposure of materials to air at atemperature of 121 C for 168 h.4.Physical Properties4.1 When tested for physical and aging requirements,heatdistortion,cold bend,U-bend discharge,surface resistivity,andtrack resistance in accordance with Test Methods D470,thetrack-resistant black crosslinked polyethylene insulation shallmeet the requirements specified in Table 1.The insulation is tomeet the requirements for percent hot creep and hot setspecified in Table 1.The test is to be performed in accordancewith ICEA T-28-562.Only in case of dispute,the solventextraction(gel content and swell ratio)test in Test MethodsD2765 is to be the referee method.The extractables,after adrying time of 20 h,shall be no more than 30%.5.Electrical Requirements5.1 Subject cable specimens to a 5 min ac or dc voltagewithstand test at voltages which are based on the nominalthickness of the insulation.Conduct tests in accordance withMethods D470 using 125 V/mil(5 kV/mm)for ac tests or 375V/mil(15 kv/mm)for dc tests.6.Sampling6.1 Sample the insulation in accordance with Test MethodsD470,D2765,and ICEA T-28-562.7.Test Methods7.1 Test the insulation in accordance with Test MethodsD470,D2132,and D2765,modified as noted in Table 1,andICEA T-28-562.1This specification is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility ofSubcommittee D09.18 on Solid Insulations,Non-Metallic Shieldings and Coveringsfor Electrical and Telecommunication Wires and Cables.Current edition approved March 1,2013.Published March 2013.Originallyapproved in 1977.Last previous edition approved in 2007 as D3555 07 DOI:10.1520/D3555-07R132For referenced ASTM standards,visit the ASTM website,www.astm.org,orcontact ASTM Customer Service at serviceastm.org.For Annual Book of ASTMStandards volume information,refer to the standards Document Summary page onthe ASTM website.3Available from The Insulated Cable Engineers Association,Inc.(ICEA),P.O.Box 1568,Carrollton,GA 30112,http:/.Copyright ASTM International,100 Barr Harbor Drive,PO Box C700,West Conshohocken,PA 19428-2959.United States1 8.Keywords8.1 ac test;cold bend;crosslinked polyethylene;dc test;elongation;environmental cracking;heat distortion.surfaceresistivity;tensile strength;track-resistant;u-bend dischargeASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentionedin this standard.Users of this standard are expressly advised that determination of the validity of any such patent rights,and the riskof infringement of such rights,are entirely their own responsibility.This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised,either reapproved or w