分享
ASTM_D_3031_-_81_1986_scan.pdf
下载文档

ID:178756

大小:918.63KB

页数:10页

格式:PDF

时间:2023-03-04

收藏 分享赚钱
温馨提示:
1. 部分包含数学公式或PPT动画的文件,查看预览时可能会显示错乱或异常,文件下载后无此问题,请放心下载。
2. 本文档由用户上传,版权归属用户,汇文网负责整理代发布。如果您对本文档版权有争议请及时联系客服。
3. 下载前请仔细阅读文档内容,确认文档内容符合您的需求后进行下载,若出现内容与标题不符可向本站投诉处理。
4. 下载文档时可能由于网络波动等原因无法下载或下载错误,付费完成后未能成功下载的用户请联系客服处理。
网站客服:3074922707
TM_D_3031_ _81_1986_scan
ASTM D303L 81 m 0757510 0028581 T m)Designation:D 3031-81(Reapproved 1986)Standard Test Method for Total Sulfur in Natural Gas by Hydrogenation This standard is issued under the fixed designation D 3031;the number immediately following the designation indicates the year of original adoption or,in the case of revision,the year of last revision.A number in parentheses indicates the year of last reapproval.A superscript epsiIon(e)indicates an editorial change since the last revision or reapproval.1.Scope 1.1 This test method covers the determination of sulfur in natural gas containing not more than 1.0 grain of sulfur/lOO d(23 mg/m3)and not more than 0.5%of Cs and heavier hydrocarbons.1.2 The values stated in inch-pound units are to be regarded as the standard.1.3 This standard may involve hazardous materials,oper-ations,and eqirbment.This standard does not purport to address all o f the safety problems associated with its use.&i s the responsibility o f the user of this standard to establish appropriate safety and health practices and determine the applicability o f regulatoiy limitations prior to me.2.Referenced Document 2.1 ASTM Standard:D 2725 Test Method for Hydrogen Sulfide in Natural Gas(Methylene Blue Method)2 3.Summary of Method 3.1 A measured sample of gas is mixed with humidified hydrogen and passed over platinum gauze at 900C in a tube furnace.Organic sulfur in the gas is converted ta hydrogen sulfide,which is absorbed in a zinc acetate solution and determined by the mefhylene blue procedure(Test Method D 2725).4.Apparatus 4.1 In addition to the apparatus specified in Test Method D 2725,the following items are required:4.1.1 Coiltrol Valves-Valves 1,2,and 5 of Fig.2 shal be needle valves or other devices suitable for regulating the flow of hydrogen and sample gas.Valves 3 and 4 shall be either quick opening and closing valves or a 3-way metal or glass cock,for rapidly diverting the sample stream.Valves 6 and 7 shall be 3-way metai or glass cocks,for diverting the gas through the liquid sample injector according to 6.5.4.1.2 Flowmeters-Variable area or capillary types,for measuring the rates of flow of sample gas at 0.2 fi3(6 L)/h and of hydrogen at 0.8 fi3(25 L)/h.The sensitivity of the sample flowmeter shall be such that a 1%change in flow can be observed.The sensitivity of the hydrogen flowmeter shall be such that a 2 9 6 change in flow can be observed.This tesf method is under the jurisdiction of ASTM Committee D-3 on Gaseous Fuels and is the direct responsibility of Subcommittee D03.05 on Determination of Special Constituents of Gaseous Fuels.Current edition approved Dec.28,1981.Published Aprii 1982.Originiaily published as D 3031-72.Last previous edition D 3031-72(1977).Annical Book oJASThf Standards,Vol 05.05.4.1.3 Pyrometer-A pyrometer of suitable design,capable of indicating the temperature at 900C within f1O”C.4.1.4 Refractory Tube,transparent fused silica tube 3/4-in.(20-mm)inside diameter,and 24 to 30 in.(60 to 75 cm)long,with reduced end for tubing connection.4.1.5 Timer-A stopwatch or other device to register periods of 15 to 30 min with an accuracy 0.02 min or better.4.1.6 Tube Furnace-The furnace shall be 9 to 12 in.(23 to 300 mm)long and capable of maintaining a temperature of 900 rr 10C in its middle 3-in.(80 mm)section.4.1.7 Liquid Sample Injector-A glass apparatus similar to that of Fig.1 containing a rubber septum for introduction of a l-mL liquid sample directly into the gas stream,and a liquid trap section which permits only vapor to leave the apparatus.Provision should be made to warm the trap area to speed evaporation of liquid.4.1.8 Syringe-A hypodermic syringe for introduction of 1.0-mL liquid sample with 2%accuracy through a rubber septum.5.Reagents and Materials 5.1 The reagents specified in Test Method D 2725 are required,as well as the following:5.1.1 Hydrogen-99.5%purity or better.It shall meet the requirements of 7.3 and 7.4.A high-pressure cylinder shall be fitted with a pressure regulator to reduce the delivery pressure to 1 to 5 psi(6.9 to 34.5 kPa)gage.5.1.2 Methyl Alcohol-Reagent grade.5.1.3 Platinum Catalyst-A 3 by 12 in.piece of platinum-10%rhodium gauze,80 mesh,0.003 in.diameter wire.NOTE l-Fused silica wool may be used at 10”C in place of the platinum catalyst.5.1.4 Sulfur Absorbers-Two activated charcoal packed absorption tubes,each approximately 3/4-in.(19 mm)diam-eter by 10 in.(250 mm)long with tubing connections on each end.NOTE 2-One of these items not required if hydrogen purity meets absorbance specifications of 7.4.5.1.5 Surfir Compound-Any mercaptan,organic sulfide,or organic disulfide is satisfactory if the compound contains 3 to 5 carbon atoms per molecule.The purity must be such that the weight of sulfur contained in the liquid compound must be known to within 1%.6.Calibration specified in Test Method D 2725.7.Preparation of Apparatus 6.1 Calibrate the spectrophotometer or colorimeter as I 7.1 Wind the platinum-rhodium gauze into a roll 3 in.(8 N

此文档下载收益归作者所有

下载文档
你可能关注的文档
收起
展开